DESCRIPTION |
TEST METHOD
& STATEMENT |
LABORATORY |
CLASSIFICATION &
RESULTS |
Bacterial and Fungal Growth Resistance |
ASTM G21-Panel
ASTM
G21-Accessories |
Biosan Laboratories |
Resistance to the following organisms:
- Aspergillus niger
- Aureobasidium pullulans
- Chaetomium globosum
- Penicillium funiculosum
- Trichoderma virens
|
Bacterial and Fungal Growth Resistance |
ASTM G22 |
Exova - Al Futtaim |
No growth for the following organisms:
Pseudomonas aeruginosa
Staphylococcus aureus |
Bacterial Growth Resistance |
ASTM E2180 |
Biosan Laboratories |
Resistance to Staphylococcus
aureus |
Fire Propagation Index |
BS 476 Part
6 |
Warringtonfire - UK |
Class "0" |
Surfaces Spread of Flame |
BS 476 Part
7 |
Warringtonfire - UK |
Class "1" |
Certification of Product
Listing No. 016 |
BS 476 Part 6,
7 |
Warringtonfire -UK, Mideast Global Safety |
Class "0" |
Certificate of Factory Production Control and Product
Labels |
Certificate of Approval
ME0016 |
Warringtonfire - UK, Mideast Global Safety |
|
Epiradiateur Test |
NFP 92-501 |
Warringtonfire - UK
(Ministere de l'Industrie et de la Decentralisation) |
M1 |
Flame Spread Index |
ASTM E-84
NFPA 255
UL 723
NFPA 101 Life Safety Code |
Commercial Testing Company - USA |
Class "A" |
Flame Spread Index |
ASTM E-84
NFPA 255
UL 723
NFPA 101 Life Safety Code |
Commercial Testing Company - USA |
Class "A" |
Smoke Developed Index |
ASTM E-84
NFPA 255
UL 723
NFPA 101 Life Safety Code |
Commercial Testing Company - USA |
Class "A" |
Toxicity Index |
NES 713
IMO Resolution MSC 61 (67) |
Warringtonfire UK
Warringtonfire UK |
5.7
Average S.O.D. <200 |
Thermal Conductivity |
ASTM C518 |
Dubai Municipality Laboratory |
0.020 w/m.k.
0.169 Btu w/m.k. ft2 |
Compressive Strength |
ASTM D1621 |
Dubai Municipality Laboratory |
220.9 kpa |
Flexural Strength |
ASTM C203 |
Dubai Municipality Laboratory |
1170 kpa |
Panel Density |
ASTM D1622 |
Dubai Municipality Laboratory |
71.5 kg/m3 |
Water Absorption Level |
ASTM C209 |
Dubai Municipality Laboratory |
0.14%
(24 hours immersion) |
Sound Attenuation Test |
UNI 8270
DIN 52210 |
Instituto Giordano |
Average SRI (100-3150 Hz) 14.1 |